UPS Start-up Service
UPS Start-Up Service Programs -- Critical Systems Services provides customers with CSSI Authorized Personnel to ensure proper start-up of your UPS system. CSSI will energize and check functionality of the system in all modes to ensure compliance with stated technical standards and manufacturer's specifications . In all cases, the system must be electrically installed prior to the start-up.
Single-phase UPS
· Verify wiring is correct
· Conduct a visual inspection of both the unpacked frame and the input/output hard wiring performed by the licensed electrician (if required).
· Load units with battery modules and power modules (if applicable).
· Clean system.
· Start up of the unit and perform a comprehensive diagnostic and self test.
Three-phase product line
· Verify wiring is correct, note any discrepancies.
· Perform visual inspection of UPS equipment to ensure that all connections are properly fixed and tight.
· Verify that all power wires are terminated in correct location, using ohm meter and physical inspection.
· Verify proper operation of all internal functions.
· Verify that all electrical wiring complies with all local/national electrical codes and regulations.
· Verify bypass operational, static and manual.
· Verify proper internal battery string voltages.
· Verify proper regulation of output waveform, and integrity of all phases.
· Record all front panel reading and parameter stacks.
· Clean system.
· Start up of the unit and perform a comprehensive diagnostic and self test.
|